Research and ACM SRC Posters Archive

HPC and AI Water Usage: Findings From 11 Leading Supercomputing Centers


Poster Type: Research Posters

Author: David Martinez (Sandia National Laboratories, Energy Efficient High Performance Computing Working Group (EE HPC WG)), Michael Ferguson (Los Alamos National Laboratory (LANL)), Tiziano Belotti (Swiss National Supercomputing Centre (CSCS)), Fumiyoshi Shoji (RIKEN Center for Computational Science (R-CCS)), Daniel Hackenberg (Technical University of Dresden), Chris DePrater (Lawrence Livermore National Laboratory (LLNL)), Mani John (King Abdullah University of Science and Technology (KAUST)), Michele Toni (European Centre for Medium-Range Weather Forecasts (ECMWF)), Suzy DiMont (National Laboratory of the Rockies (NLR)), David Grant (Oak Ridge National Laboratory (ORNL), Energy Efficient High Performance Computing Working Group (EE HPC WG)), Hiren Ghandi (Leibniz Supercomputing Centre (LRZ)), Matthew Anderson (Idaho National Laboratory), Steve Gu (Reed College), Natalie Bates (Energy Efficient High Performance Computing Working Group (EE HPC WG))

Abstract: High-density artificial intelligence (AI) and high performance computing (HPC) workloads are increasing thermal loads and making water use an important facility consideration. This study establishes an operational baseline from 11 large HPC facilities using a 35-question survey covering cooling systems, water consumption, WUE, blowdown, water quality, and conservation barriers. Facilities with hybrid/adiabatic cooling report a lower WUE, indicating higher water efficiency among surveyed sites, while evaporative facilities generally reported higher WUE. Cooling-tower blowdown accounted for approximately 15%–33% of facility water use at surveyed evaporative sites. Higher cycles of concentration (CoC) can reduce water use, but water chemistry can limit operation. The study also identified a definite water-energy trade-off, particularly during peak summer conditions. Finally, closed-loop liquid cooling does not necessarily eliminate on-site water use; water consumption depends on the outdoor heat-rejection method.

Best Poster Finalist (BP): no
Poster: PDF
Poster Summary: PDF


Back to Poster Archive Listing