Author: Shrenik Jadhav (Embry-Riddle Aeronautical University), Zheng Liu (University of Michigan-Dearborn), Vidhyashree Nagaraju (Embry-Riddle Aeronautical University)
Abstract: Exascale cooling plants are often sized and operated by convention, making it unclear how much energy can be recovered through control and how much performance is fixed by plant design. We developed and validated a digital twin of the Frontier supercomputer cooling plant using one year of operational telemetry, then optimized control settings, coolant flow, subloop topology, and life cycle cost and carbon. The novel contribution is an end-to-end co-design framework showing that implementable control recovers 27.8% of annual cooling energy, while optimized flow allocation reduces topology sensitivity by 93%, leaving embodied carbon as the main remaining design criterion.
The study has completed model validation, annual optimization, topology enumeration, and life cycle analysis. During the poster session, we will use a system diagram, validation plots, energy savings comparisons, topology results, and a life cycle decision map to show why control should be optimized before hardware redesign.